What CoolIT’s rating measures

At SC26 on November 16, 2026, Ecolab announced that its 3D TRASAR monitoring is integrated into the CoolIT CHx 3000 coolant distribution unit (CDU). CoolIT rates the unit to transfer 3 megawatts of heat at a 3°C approach temperature difference. The figure measures cooling capacity under stated conditions. It does not tell you how much electricity the unit draws or how much energy a site would save.

Ask for the vendor’s exact test definition

A liquid-to-liquid CDU transfers heat from the equipment coolant to the facility loop through a heat exchanger. The approach temperature is the difference between two specified temperatures on opposite sides of that exchanger. Ask which two readings CoolIT uses at the rated condition and where the sensors sit.

Use the curve for your actual operating point

A headline rating is not a substitute for the applicable performance curve. If facility supply water is warmer than the test condition, if flow changes, if coolant properties differ, or if a pump or one CDU is out of service, the delivered cooling capacity can change. In those cases, read the vendor’s curve for the actual conditions instead of applying the headline number or inferring a simple numeric derate.

A simple comparison at a real site condition

Suppose the vendor’s witness test used cooler facility water than your site sees in summer. Ask for the capacity curve for your summer supply temperature, expected flow and specified coolant. Compare that capacity with the planned heat load. If the curve does not cover your conditions, ask for a test at the agreed point.

What to ask before you accept the rating

  • What is the vendor’s exact definition of the 3 MW rating?
  • Where are the temperature and flow sensors located for the published test?
  • What were the facility-loop and equipment-loop conditions at the stated approach temperature?
  • Which performance curve applies to my actual supply temperature and flow?
  • What happens to capacity if one pump or one unit is out of service?
  • Can we witness a test at our agreed operating point, and which temperatures, flows and loads will be recorded?
  • Are coolant quality monitoring alerts routed separately, and to whom?

Why this matters for procurement

For procurement, ask the vendor to show the expected heat transfer at your facility’s operating point and state the remaining capacity if one unit is unavailable. Confirm coolant monitoring and alert routing separately.

Ecolab announcement at SC26

CoolIT CHx 3000 product page